Circuit Breaker
5925000889501 000889501 70-760-8AMP AM-12-760-8AMP
A device with means other than fuses for automatically opening the circuit in which it is installed when the current varies from the predetermined value for which the device is set. May include provisions for manual operation. At least one set of contacts must be in series with the actuating element(s). A combination of semiconductor and passive devices may be used in lieu of contacts. For automatically operated items in which the actuating (tripping) element and contacts are not in series, see RELAY (as modified). For items which are operated both manually and automatically but the actuating elements and contact are not in series, see RELAY-SWITCH. Excludes CIRCUIT BREAKER BOX and magneto "breaker" assemblies. See also SWITCH (as modified); and CONTROLLER. View more Circuit Breaker
January 2023
30
Marketplace 5925-00-088-9501
Request a Quotation from participating marketplace vendors
Restrictions 5925-00-088-9501
5925-00-088-9501 is a Circuit Breaker that does not have a nuclear hardened feature or any other critical feature such as tolerance, fit restriction or application. Demilitarization of this item has been confirmed and is not currently subject to changes. This item is considered a low risk when released from the control of the Department of Defense. The item may still be subject to the requirements of the Export Administration Regulations (EAR) and the Code of Federal Regulations (CFR). This item may be hazardous as it is in a Federal Supply Class for potentially hazardous items. A MSDS should be available from the supplier for the end user to evaluate any hazards. The precious metals content of this item is unknown.
Import and Export 5925-00-088-9501
- Schedule B
- Subscribe to View Schedule B
- HTS Code
- Subscribe to View HTS Code
End Users 5925-00-088-9501
- Kuwait (YK01)
- Effective Date:
- 1 Feb 2015
- France (ZF01)
- Effective Date:
- 1 May 2015
- Republic of Korea (ZH01)
- Effective Date:
- 1 Apr 1991
Approved Sources 5925-00-088-9501
- Part Number
- Manufacturer
- Status
- 70-760-8AMP
- Manufacturer
- 74193 - Eaton Corp (Obsolete)
- Original Design
- Original Design
- AM-12-760-8AMP
- 74193 - Eaton Corp (Obsolete)
- Canceled/Obsolete
- Canceled/Obsolete
Datasheet 5925-00-088-9501
- Characteristic
- Specifications
- FIIG
- Specifications
- A030A0
- Actuator Function [CPRW]
- Trip-Reset
- Actuator Position Designation [CPRX]
- At Pole One
- Arc Quenching Method [APNQ]
- Magnetic Blowout
- Body Length [ADAQ]
- 2.490 Inches Minimum And 2.510 Inches Maximum
- Body Style [AAQL]
- Single Pole Type
- Body Width [ADAT]
- 0.740 Inches Minimum And 0.760 Inches Maximum
- Boss Height [AJEC]
- 0.130 Inches Minimum And 0.150 Inches Maximum
- Case Material [ADTV]
- Plastic
- Center To Center Distance Between Terminals Parallel To Length [AEBP]
- 1.928 Inches Minimum And 1.948 Inches Maximum
- Circuit Protection Type [CPRH]
- Overcurrent Single Location
- Distance Between Centerlines Of Mounting Facilities Parallel To Body Length [AEBY]
- 2.052 Inches Minimum And 2.072 Inches Maximum
- Fragility Factor [AFJN]
- Moderately Rugged
- Maximum Continuous Load Current Rating Per Pole [CPLM]
- 8.0 Amperes Dc Single Location
- Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps [CPRG]
- 3000.0 Dc Single Location
- Mounting Facility Type And Quantity [AXHR]
- 2 Threaded Stud
- Mounting Surface To Terminal End Distance [AJWX]
- 2.461 Inches Minimum And 2.481 Inches Maximum
- Nominal Thread Size [CQJX]
- 0.138 Inches
- Operating Voltage Type And Rating Per Pole In Volts [CPRF]
- 32.0 Dc Single Location
- Inclosure Protection Type For Which Designed [CQXF]
- Fungus Resistant
- Internal Trip Release Configuration [CPSM]
- Series Trip Single Location
- Main Contact Tripping Mechanism Type [CPRR]
- Trip Free
- Manual Actuator Type And Quantity [CPRT]
- 1 Toggle
- Pole Quantity [AKPX]
- 1
- Reset Method [CPRQ]
- Manual
- Trip Delay Time In Seconds Per Rated Continuous Current [CQWN]
- 8.000 Minimum At 125 Pct Single Location And 4.000 Maximum At 200 Pct Single Location
- Trip Release Characteristic [CPRL]
- Time Delay Single Location
- Trip Release Method [CPRJ]
- Magnetic-Hydraulic Single Location
- Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent [CPRN]
- 125.0 Single Location
- Storage Type [BBRG]
- General Purpose Warehouse
- Terminal Type And Quantity [TTQY]
- 2 Threaded Stud
- Thread Quantity Per Inch [CMLP]
- 32
- Thread Series Designator [THSD]
- Unc
DLA Procurement Analysis 5925-00-088-9501
Management Data 5925-00-088-9501
- Effective Date
- Organization
- Unit of Issue
- Unit Price
- Qty Unit Pack
- Unit of Issue
- Jul 1989
- Defense Logistics Agency (DS)
- EA
- Subscribe
- 1
- EA
- MOE
- USC
- Code
- Statement
- Order of Use
- Jump To Code
- Qty Per Assy
- UOM
- Technical Document
- Quantative Expression
- Code
- Defense Logistics Agency (DS)
- I
- Z
- Discontinued-Use 5925-00-487-6532
- Z
NATO Stock Numbers Related to 5925-00-088-9501
Freight Information 5925-00-088-9501
5925-00-088-9501 has freight characteristics.It has a National Motor Freight Classification (NMFC) of 061300. A Sub NMFC of X. It has a NMFC Description of CIRCUIT BREAKER/SWITCH NOI. 5925-00-088-9501 is rated as class 77.5 when transported by Less-Than Truckload (LTL) freight. It has a Uniform Freight Classification (UFC) number of 34410 which rates the freight between FCL and LCL. 5925-00-088-9501 has a variance between NMFC and UFC when transported by rail and the description should be consulted. It has a Water Commodity Code (WCC) of 658 for ocean manifesting and military sealift. 5925-00-088-9501 is not classified as a special type of cargo when transported by water. 5925-00-088-9501 is not a consolidation and does not exceed 84" in any dimension. It should be compatible with a standard 72" Aircraft Cargo Door when transported by air.
Contracting Technical Data File (CTDF) 5925-00-088-9501 October 2021
Criticality and Quality
- Critical Item Code:
- Flight Safety:
- Life Support:
- Certified Samples:
- Serialization:
- First Article Test (FAT):
- Certificate of Quality Compliance:
- Production Lot Testing:
- Special Testing:
- Qualified Products List (QPL):
Commercial Properties
- Government Furnished Material:
- Government Furnished Tooling:
- Government Furnished Property:
- Price Evaluation Code:
- Diminshing Manufacturing Sources:
- Warranty:
- Commerical Off The Shelf (COTS):
- End Item Application:
- Auctioning Candidate:
- Source of Procurement:
- Contract Option:
Restrictions
- Boeing Rights Guard:
- Export Controlled:
- Controlled Technical Data Package (TDP):
- Restricted Technical Data Package (TDP):
- Contains Classified Material
- Weapons System Indicator Code (WSIC):
- N
Packaging Requirements
- Packaging Determination Table:
- Packaging Review Code:
- Special Packaging Instruction Number (SPIN):
- Special Packaging Instruction Number Revision:
- Special Packaging Instruction Number Date:
- Pallet Reference Number Required: